Shear Capacities for Wood-Framed Diaphragms

Last updated October 30, 2024
By Aidan Phelan

Based on SDPWS 2015 (Table 4.2). All specifications based on min. 19/32 floor sheathing, 12″ field nailing. All SDPWS shear values multiplied by 0.5 * (1 – (0.5 – 0.42)) to convert to ASD and adjust for SPF framing. Unblocked shear values show All other Cases / Case 1, in order to achieve higher sheathing each loading direction must be analyzed separately.

NailsBlockingJoistNail SpacingVs (plf)Ga (k/in) (ply)
0.148×3Unblocked2x6” all supported edges197/2628.5
0.148×3Unblocked3x6” all supported edges220/2947.5
0.148×3Blocked2x6” all edges29414
0.148×3Blocked3x6” all edges33112
0.148×3Blocked2x4” diaphragm boundary and continuous panel edges, 6” other panel edges3919.5
0.148×3Blocked3x4” diaphragm boundary and continuous panel edges, 6” other panel edges4418